CORDS LowTox - Fire Retardant Low Smoke Cables
These cables are specially designed for hazardous areas where during fire low HCL gas emission & smoke are essential. These cables are also Fire Retardant. LV Power, Control, Instrumentation and Thermocouple cables can be manufactured as per various National/International standards.
| Properties of FRLS Compounds | |
|---|---|
| Min. oxygen index as per ASTMD-2863 | 29% |
| Min. temperature index as per ASTMD-2863 | 250°C |
| Max. HCL emission as per IEC-60754-1 | 20% by weight |
| Max. Smoke density rating as per ASTMD-2843 | 60% |
| Flammability test on completed cables | Cables shall meet the test requirements of IEC-60332-1, IEC-60332-III Cat A, B or C, IEEE-383, SS-424 1475 Cl. F3, IS:10810-53, 61 or 62 as per customer requirements |